| Specifications |
NB50000c-cg |
Altitude
|
Operating: 10,000 ft (3,000 m) maximum Nonoperating: 30,000 ft (9,144 m) maximum
|
Temperature
|
Operating: 5°C to 40°C (41°F to 104°F) Nonoperating: --40°C to 70°C (-40°F to 158°F)
|
Humidity
|
Operating: 5% to 85% relative non-condensing maximum Nonoperating: 93% maximum
|
Dimensions
|
Height: 72 in (182.9 cm) Width: 27 in (68.6 cm) Depth: 39.4 in (1 m)
|
Weight
|
1,200 lb (907.2 kg)
|
Power supply
|
Typical power dissipation: 6,239 VA Input current: 28 A @ 208 VAC AC input power: 200–240 V, 50–60 Hz
|
Safety
|
Compliant with UL 60950-1/CSA C22.2 NO. 60950-1-03 and EN 60950
|
Electromagnetic interference
|
Complies with FCC rules and regulations, Part 15, as a Class A Digital Device; manufacturer’s declaration to EN 55022 Level A
|
Power line LF emissions
|